Register Contents

Channel values in integer format

Register

Type Contents

Range

0000

ro/rw

Channel 1 integer value -32768 ... 32767

0001

ro/rw

Channel 2 integer value -32768 ... 32767

:

:

:

:

0007

ro/rw

Channel 8 integer value -32768 ... 32767

:

:

:

:

001F

ro/rw

Channel 32 integer value -32768 ... 32767

Channel values in real format

Register

Type Contents

Range

0020

ro/rw Channel 1 real high word

0 ... 65535

0021

ro/rw Channel 1 real low word

0 ... 65535

0022

ro/rw Channel 2 real high word

0 ... 65535

0023

ro/rw Channel 2 real low word

0 ... 65535

:

:

:

:

002E

ro/rw Channel 8 real high word

0 ... 65535

002F

ro/rw Channel 8 real low word

0 ... 65535

:

:

:

:

005E

ro/rw Channel 32 real high word

0 ... 65535

005F

ro/rw Channel 32 real low word

0 ... 65535

Attention: The low word and the high word of a channel must
always be read or written simultaneously.