beautypg.com

Kipp&Zonen COMBILOG Data Logger User Manual

Page 134

background image

Preset Multiple Register

Description:
By this command a large, continuous field of registers can be
written.

Request Telegram

ADR FNR REGSTA REGNUM BYT-

NUM

D0

10

MSB LSB MSB LSB

...

Dn CRC

MSB LSB

Response Telegram

ADR

FNR

REGSTA

REGNUM

CRC

10

MSB

LSB

MSB

LSB

MSB LSB

ADR ............ module address (hex 00..7F)
FNR ............ function number (hex 10)
REGSTA ..... address of the first register to be written
REGNUM .... number of registers to be written
BYTNUM ..... number of data bytes (max. 64)
D0 - Dn ....... data bytes (max. 64)
CRC ............ check sum
CRC polynomial: u

15

+ u

13

+ 1

CRC start value: hex FFFF

Hardware Manual COMBILOG 1022

134