5.2.3

Progressive Counter

When configuring a digital input as a progressive counter the
data logger COMBILOG 1022 constantly monitors the digital
input for a signal variation. If a negative signal edge (1

-

> 0) oc-

curs at the input, the current result is increased by 1.

The values may range from -2

31

to +(2

31

-1) (about -2.1 to +2.1

billion). Above +2

31

-1 the counting continues with -2

31

. The val-

ues can be reset to zero via the bus interface or internally after
the procedure of the averaging interval.

Note: The maximum counting rate is 2400 Hz.

Note: After a voltage cut-off the counter is reset to zero.

Figure 5.12 Progressive Counter

+1

+1

+1

+1

+1

n+1

n+2

n+3

n+4

n+5

signal diagram:

I/O 1

counting

counting

measurand

pulse

Hardware Manual COMBILOG 1022

50

Anschlussschema

Schaltung

0V

I/O

+ 10V .. 30V

Connection scheme

Circuit