beautypg.com

Kipp&Zonen COMBILOG Data Logger User Manual

Page 86

background image

RUN

(green LED)

ERR

(red LED)

meaning

off

The supply voltage has been selected too low or

the power supply cannot supply the required

power.

off

flash

The data logger is in the monitor mode. A valid

program has not yet been loaded; the appliance is

not yet ready for operation.

on

There is a sensor error detected. Possible causes

may be: 1. wrong configuration, 2. line break or

short circuit, 3. measured value too high or too

low.

flash

flash

The data logger is in the download mode. Cur-

rently a program or a configuration is transmitted

to the data logger.

on

off

The supply voltage has been connected correctly.

There is no error. Data transmission to the module

via bus is not active.

on

There is a sensor error detected. Possible causes

may be: 1. wrong configuration, 2. line break or

short circuit, 3. measured value too high or too

low.

short off

X

A telegram has just been dispatched from the

data logger via the bus to a control system or to a

PC.

Table 9.1 Assignment of LED functions (flash frequency approx. 1Hz)

Hardware Manual COMBILOG 1022

86