beautypg.com

Kipp&Zonen COMBILOG Data Logger User Manual

Page 133

background image

Diagnostic

Description:
By this command a diagnostic telegram will be sent to the data
logger. If the telegram has been received in correct form the
module will send this telegram back unchanged (echo tele-
gram).

Request Telegram

ADR

FNR

SUBFCT

DATA

CRC

8

00

00

A5

37

MSB LSB

Response Telegram

ADR

FNR

SUBFC

DATA

CRC

8

00

00

A5

37

MSB LSB

ADR ............ module address (hex 00..7F)
FNR ............ function number (hex 08)
SUBFCT ..... sub function number (hex 0000)
DATA .......... data word (hex A537)
CRC ............ check sum
CRC polynomial: u

15

+ u

13

+ 1

CRC start value: hex FFFF

Hardware Manual COMBILOG 1022

133