9.3 Startup

Checklist and

Warnings

CAUTION: If equipped with a cooling module with reheat, the

crankcase heater must be allowed to warm up for at least 24 hours

prior to startup. Disable cooling controls before turning on power

to warm up crankcase heaters. See Hazard Levels, page 2.

Close and latch the doors.

IMPORTANT: If equipped with digital controls, when turning on the main controller

for the first time, be sure to push and hold the Function Key for five seconds. This

should cause the first LED to light. If the LED light is lit, the controller will remain

on and allow for remote control even after a power outage. If the LED light is not

lit, it will be necessary to restart the controller at the unit after a power outage.

Read and follow the preparation instructions below on power supply voltage

phasing. When ready, turn on the power. Turn on the gas.

Power Supply Voltage Phasing

Because it is possible to unknowingly connect 3-phase power in such a way

as to cause the blower and, if there is an optional reheat compressor, the

scroll compressor to rotate in reverse. It is very important to check this on

startup.

Blower Rotation - Check rotation on startup. If blower rotation is not correct, reverse

by interchanging two wires on the 3-phase supply connection to the blower motor.
Check Reheat Compressor (if equipped) - Connect refrigerant pressure gauges

to the suction and discharge lines of the compressor and an electric meter to the

power supply.

CAUTION: Be sure to connect pressure gauges to the suction

and discharge lines before system startup so that compressor

rotation can be checked immediately. A scroll compressor will

be destroyed if allowed to operate in the wrong direction. See

Hazard Levels, page 2.

Adjust the controller so that a call for reheat exists. Immediately at startup,

observe the gauges. If the suction pressure rises and discharge pressure

drops, the compressor is operating in reverse and must be shut down. Turn

off the power and switch the 3-phase line voltage wiring connections before

restarting the unit.
(Important NOTE:
If allowed to operate for several minutes in reverse, the

compressor’s internal protector will trip. If a compressor is repeatedly allowed to

restart and run in reverse, the compressor will be permanently damaged.)

9.2.4 Cooling Checklist Prior to Startup (PXH, PDH, SDH, SHH,

and PEH with cooling module ):

Verify that the condensate drain(s) are connected and properly trapped. See

Paragraph 6.2 and 6.6.3.

Verify that the refrigerant circuits are charged with the appropriate refrigerant and

leak tested according to the condensing unit instructions.

Check heat section operation.

WARNINGS

For your safety, read before operating. If you do not follow these

instructions exactly, a fire or explosion may result causing property

damage, personal injury, or death.

• Models SDH, PDH, SHH - This appliance does not have a pilot. It is

equipped with an ignition device which automatically lights the burner. Do

not try to light the burner manually.