Form I-PDH/SDH/PEH/SHH/PXH, Page 17

FIGURE 10 -

High Altitude

(>6000ft/

1830M)

Pressure

Switch

Requirement

Pressure

Switch

NOTE: If elevation is above 6000 ft

(1830M) and the following conditions apply,

installation of a high altitude pressure

switch is required. When a replacement

switch is needed, contact your distributor

for the switch and follow the instructions

below to install the high altitude pressure

switch before starting the heater.

PDH or SDH Size installed

above 6000 ft (1830M)

Switch

P/N

Label

Color

Setting

75, 100

197031

Purple

0.35” w.c.

125

197032

Pink

0.45” w.c.

150

197029

Lt Blue

0.60” w.c.

175, 200, 225, 250, 300, 350, 400A

201160

Brown

1.05” w.c.

Derate by Valve Outlet

Pressure Adjustment

if needed for High

Altitude Operation

Instructions for High Altitude Derate - Models PDH, SDH, and SHH

1. Refer to TABLE 10, and determine the required valve outlet pressure(s) for the

elevation where the heater will be operating. If unsure of the elevation, contact the

local gas supplier. If unsure of the type of gas control, check the option list on the

unit wiring diagram.

If the elevation on the rating plate does not match the elevation of the installation site,

follow these instructions to adjust the valve.

TABLE 10 - Valve Outlet

Pressure Settings by

Elevation for Models

PDH, SDH, and SHH
(Does NOT apply to

Option AG58 or D12G --

see NOTE on page 16.)

Instructions for changing pressure switch:

1. If the unit is installed, turn off the gas and the power.

2. In the control compartment, locate the pressure

switch that needs to be replaced. (

NOTE: If there are

two pressure switches, the high speed switch to be

replaced is toward the top of the unit.)

3. Mark and disconnect the two wires attached to the

pressure switch.

4. Mark and disconnect the sensing tube(s) from the

pressure switch.

5. Locate the two screws holding the switch mounting

bracket. Remove the pressure switch. Save the

screws.

6. Using the same screws, install the high altitude

pressure switch. Attach the sensing tube(s) and wires.

7. If the unit is installed, turn on the power and the gas.

Model is SDH or PDH

Elevation on the rating plate is not above 6000 ft (1830M)

Unit has a single or two-stage gas control (Option AG1,

AG2, AG3, AG15, AG16, AG60, AG61, DG1, DG5, or

D12C).

NOTE: If equipped with a two-stage control with

a two-speed venter (Options AG8, AG9, AG9H, AG60,

AG61, DG1, DG5, and D12C), there are two pressure

switches. Only the high speed pressure switch needs to be

changed.

2. Locate the 1/8” outlet pressure tap on the valve (FIGURE 6). Turn the knob or

switch on the top of the valve to “OFF”. Connect a manometer to the 1/8” outlet

pressure tap in the valve. Use a water column manometer that is readable to the

nearest tenth of an inch. When making the adjustment, turn the adjustment screw

IN (clockwise) to increase pressure or OUT (counterclockwise) to decrease.

Outlet Pressure Settings (inches w.c.) by Altitude for Installation in the UNITED STATES

Altitude

Full Rate Outlet

Pressure (Single-

Stage & 2-Stage

High Fire) - Applies

to Options AG1,

AG2, AG3, AG15,

AG16, AG60, AG61,

AG62, DG1, DG5,

D12C, D12F

Full Rate Outlet Pressure with

Electronic Modulation - Applies to

Options AG8, AG9, AG9H, AG40, DG2,

DG6, and D12B (measured at the outlet

pressure tap just behind the orifice

adapter when there is a minimum

of a 20VDC signal at the electronic

modulating valve)

NOTE: Options do not apply to SHH.

2-Stage Low-Fire

Outlet Pressure -

Applies to Options

AG2, AG3, AG15,

and AG16

2-Stage Low-Fire

Outlet Pressure

with Venter

Motor Controller

- Applies to

Options AG60,

AG61, AG62, DG1,

DG5, D12C

Factory-Set

Bypass Pressure

with Electronic

Modulation

- Applies to

Options AG40,

DG2, DG6, D12B

FEET

METERS

Natural

Gas

Propane

Natural

Gas

Propane

Natural

Gas

Propane Natural

Gas

Propane Natural

Gas

Propane

0 - 2000

0 - 610

3.5

10.0

3.5

10.0

1.8

5.0

0.40

1.8

0.25

1.8

2001 - 3000

611 - 915

3.1

8.8

3.1

8.8

1.6

4.4

0.35

1.5

0.25

1.8

3001 - 4000

916 - 1220

3.0

8.5

3.0

8.5

1.5

4.2

0.34

1.4

0.25

1.8

4001 - 5000

1221 - 1525

2.8

8.1

2.8

8.1

1.5

4.1

0.32

1.4

0.25

1.8

5001 - 6000

1526 - 1830

2.7

7.7

2.7

7.7

1.4

3.9

0.31

1.3

0.25

1.8

6001 - 7000

1831 - 2135

2.6

7.4

2.6

7.4

1.3

3.7

0.30

1.3

0.25

1.8

7001 - 8000

2136 - 2440

2.5

7.1

2.5

7.1

1.3

3.5

0.28

1.2

0.25

1.8

8001 - 9000

2441 - 2745

2.4

6.7

2.4

6.7

1.2

3.4

0.27

1.1

0.25

1.8

Outlet Pressure Settings (inches w.c.) by Altitude for Installation in CANADA

Altitude

Full Rate Outlet

Pressure (Single-

Stage & 2-Stage

High Fire) - Applies

to Options AG1,

AG2, AG3, AG15,

AG16, AG60, AG61,

AG62, DG1, DG5,

D12C, D12F

Full Rate Outlet Pressure with

Electronic Modulation - Applies to

Options AG8, AG9, AG9H, AG40, DG2,

DG6, and D12B (measured at the outlet

pressure tap just behind the orifice

adapter when there is a minimum

of a 20VDC signal at the electronic

modulating valve)

NOTE: Options do not apply to SHH.

2-Stage Low-Fire

Outlet Pressure -

Applies to Options

AG2, AG3, AG15,

and AG16

2-Stage Low-Fire

Outlet Pressure

with Venter

Motor Controller

- Applies to

Options AG60,

AG61, AG62, DG1,

DG5, D12C

Factory-Set

Bypass Pressure

with Electronic

Modulation

- Applies to

Options AG40,

DG2, DG6, D12B

FEET

METERS

Natural

Gas

Propane

Natural

Gas

Propane

Natural

Gas

Propane Natural

Gas

Propane Natural

Gas

Propane

0 - 2000

0 - 610

3.5

10.0

3.5

10.0

1.8

5.0

0.4

1.8

0.25

1.8

2001 - 4500

611 - 1373

2.8

8.1

2.8

8.1

1.5

4.1

0.3

1.4

0.25

1.8