beautypg.com

0 mechanical (cont’d), 4 optional mixing box) (cont’d), Operating sequence with economizer option – Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 28: 3 mixing box damper and control options (cont’d)

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 28

FIGURE 20B - Partial Psychometric Chart for Setting

Economizer Logic Module (Reprinted with permission from

Honeywell)

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX. °F (°C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

90

10

0

80

70

60

50

40

30

20

10

ENTHALPY—BTU PER POUND DR

Y AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

APPROXIMATE DRY BULB TEMPERATURE— °F (°C)

A

A

B

B

C

C

D

D

M11160C

RELA

TIVE HUMIDIT

Y

(%)

1

1

HIGH LIMIT CURVE FOR W7210D, W7212, W7213, W7214, W7340B.

Option GE21 - Use this

chart to set economizer

logic module.

Option GE22 - Set

economizer logic module

to “D” as shown on chart.

Operating Sequence with Economizer Option

Turn on the power and, if applicable, the gas.

On a call for low stage cooling:
1. The blower motor is energized.

2. With the outdoor enthalpy lower than the return air enthalpy:

a) The stage 1 and 2 cool circuits are locked out.

b) Dampers are positioned by the economizer and

mixed air sensor.

3. With outdoor air enthalpy higher than the return air enthalpy:

a) The stage 1 cool circuit is energized.

b) Dampers are positioned for minimum outside air.

c) On a call for high stage cooling, the stage 2 and 3 circuits are staged

appropriately

6.4.4.3 Mixing Box Damper and Control Options (cont’d)

6.4.4 Optional Mixing Box) (cont’d)

6.0 Mechanical

(cont’d)