beautypg.com

Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 27

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 27

Enthalpy Sensor(s) -

Field installed to

control dampers in

economizer Options

GE21 and GE22) - PDH,

SDH, PEH, PXH, SHH

Option GE21 requires installation of one sensor; Option GE22 requires installation of

two sensors. A system with Option GE21 includes one field-installed parts bag. A sys-

tem with Option GE22 includes two field-installed parts bags. Locate the parts bag(s)

shipped inside the unit.

TABLE 18 - Components

in each Parts Bag, P/N

220686 (GE21 requires one

parts bag; GE22 requires

two.)

1. Turn off the power. Turn off the gas (Models PDH, SDH, SHH).

2. Install the Outside Air Enthalpy Sensor - Options GE21 and GE22

a)

Attach the Sensor in the Outside Air Ductwork

Position the sensor on the inside of the outside air ductwork. The sensor may

be mounted in any orientation but must be located so that it is exposed to freely

circulating air and must be protected from rain, snow, and direct sunlight. Position

the sensor in a central location and attach with the two screws provided.

b)

Wire the Sensor

Connect the two wires to the sensor as shown on the wiring diagram. Drill a 5/8”

hole in the outside air damper mounting frame as illustrated in

FIGURE 20A. Insert

the strain relief bushing. Bring the wires through the opening and route them to

the bottom of the electrical box. Use the stick-on wire holders to prevent the wires

from interfering with the damper operation. Insert a strain relief bushing in a hole in

the bottom of the electrical box and route the wires through. Make connections at

the economizer logic module as shown on the wiring diagram.

Options GE21 and GE22

- Drill a 5/8” hole in

the outside air damper

mounting frame.

Option GE22 - Drill a

5/8” hole in the return air

damper mounting frame.

Economizer

Logic Module,

P/N 220637

FIGURE 20A - Mixing Box

with Optional Economizer

Logic Module

3. Install the Return Air Enthalpy Sensor in the

Return Air Duct - Option GE22

a)

Attach the Sensor

Position the sensor on the inside of the return air

duct. The sensor may be mounted in any orientation

but must be located so that it is exposed to freely

circulating air. Position the sensor in a central location

on the side of the duct and attach with the two screws

provided.

b)

Wire the Sensor

Connect the two wires to the sensor as shown on

the wiring diagram. Drill a 5/8” hole in the return air

damper mounting frame as illustrated in

FIGURE

20A. Insert the strain relief bushing. Bring the wires

through the opening and route them to the bottom of

the electrical box. Use the stick-on wire holders and

the wire ties to prevent the wires from interfering with

damper operation. Insert a strain relief bushing in a

hole in the bottom of the electrical box and route the

wires through. Make connections at the economizer

logic module as shown on the wiring diagram.

Installation of Option GE22 is complete. Refer to

FIGURES 20B and 20C to set the economizer logic

module.

Enthalpy Control

Sensor Installation

Instructions

Installation of Option GE21 is complete. Refer to

FIGURES 20B and 20C to set the

economizer logic module.

If installing a return air sensor (Option GE22), continue to Step 3 (below).

Qty

Component Description

P/N

1

Enthalpy Sensor, Honeywell #C7400A1004

196290

1

Blue Wire Assy, 18 ga x 72” with terminals

220621

1

Purple Wire Assy, 18 ga x 72” with terminals

220620

2

Screws, #6 x 3/4” long

110650

2

5/8” Strain Relief, Heyco #SR6N-4

100392

4

Stick-on Wire Retainers, Fastex #8511-29-00

142678

2

Plastic Wire Ties

20913