beautypg.com

Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 37

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 37

CAUTION: Joint where supply air duct attaches to the furnace must be sealed securely to

prevent air leakage. Leakage can cause poor combustion, shorten heat exchanger life, and

cause poor performance. See Hazard levels, page 2.

Requirements and

Recommendations

for Connecting and

Installing Discharge

Ductwork - All Models

• Type of Ductwork - The type of duct installation to be used depends in part on the

type of construction of the roof (whether wood joist, steelbar joist, steel truss, pre-

cast concrete) and the ceiling (whether hung, flush, etc.).

• Ductwork Material - Rectangular duct should be constructed of not lighter than

No. 26 U.S. gauge galvanized iron or No. 24 B & S gauge aluminum.

• Ductwork Structure - All duct sections 24 inches (610mm) or wider, and over 48

inches (1219mm) in length, should be cross broken on top and bottom and should

have standing seams or angle-iron braces. Joints should be S and drive strip, or

locked.

Through Masonry Walls - No warm air duct should come in contact with masonry

walls. Insulate around all air ducts through masonry walls with not less than 1/2”

(1” is recommended) of insulation.

• Through Unheated Space - Insulate all exposed warm air ducts passing through

an unheated space with at least 1/2” (1” is recommended) of insulation.

Duct Supports - Suspend all ducts securely from adjacent buildings members. Do

not support ducts from unit duct connections.

• Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a

satisfactory heating installation. The recognized authority for such information is

the Air Conditioning Contractors Association (www.acca.org), 2800 Shirlington

Road, Suite 300, Arlington, VA 22206. A manual covering duct sizing in detail may

be purchased directly from them.

CAUTION: An external duct system static pressure not within the

limits shown on the rating plate, or improper motor pulley or belt

adjustment, may overload the motor. See Hazard Levels, page 2.

• Removable Panel (See FIGURE 31.) - The ductwork should have a removable

access panel. This opening must be accessible when the furnace is in service and

should be large enough to view smoke or reflected light, to detect the presence of

leaks in the heating equipment, and to check for hot spots on the heat exchanger

due to poor air distribution or lack of sufficient air (cfm). The cover for the opening

must be attached in such a manner as to prevent leakage.

• Horizontal Discharge Duct Length - A minimum horizontal duct run of 24”

(610mm) is recommended before turns or branches are made in the duct system

to reduce losses at the furnace outlet.

FIGURE 31 -

Connecting Discharge

Ductwork

(1) If the heater has an optional duct flange, the flanges turn out as shown. (2) Shape duct connection as shown

with “U” on top and bottom and “L” on sides.

(3) Provide for sealed access panel in the ductwork. This opening must

be accessible when the furnace is in service and should be large enough to view smoke or reflected light, to detect

the presence of leaks in the heating equipment, and to check for hot spots on the heat exchanger due to poor air

distribution or lack of sufficient air (cfm). The cover for the opening must be attached in such a manner as to prevent

leakage.

(4) Slide “U” channels over top and bottom flanges on the heater. (5) Form field-supplied “U” channels over

side connections to seal. Drill and lock with sheetmetal screws.

Heater

Duct

Access Panel

in Duct

1

2

3

4

“U” Channel

(see englared

view on the right)

Furnace

Duct

“U” Channel of

Light Gauge Metal

5