beautypg.com

4 ignition system - models pdh, sdh, and shh – Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 59

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 59

Side View - PEH

Airflow

SCR Control

and Heatsink

Locations

Blower

Electrical

Electric

Heat

Section

DANGER

High voltages are present

on the terminals of the

SCR power controller(s).

SCR Power Control and Heatsink

in Option D12D (one or two

required depending on amps)

FIGURE 50 - Locations of the SCR Power Controls with

Heatsinks on Model PEH w/ith Modulating Heat Control Option D12D

WARNING

The heatsink on the SCR power controllers is HOT to the touch.

Options D12B, D12C, D12D, D12E, and D12G include an outside air relative humidity

transmitter. Depending on whether the unit includes a mixing box, the sensor is either

factory-mounted in the mixing box or shipped separately for field installation in the inlet

duct. The sensor sequences compressor operation based on outdoor dewpoint. It is

recommended for humid and temperate climates.

Relative Humidity

Sensor

“ESC or Move Back”

Push for Menus

“OK” or “Enter”

Push to Select/Accept

“Scroll Buttons”

Display Lights

Symbol and 01 - 08

Unit ON/OFF

Alarm

Comp #1 ON

Reheat ON

Comp #1 ON

Not Used

Stg #1 Heat ON Not Used
Stg #1 Heat ON Not Used

Option CL67, P/N 260599,

Space Temperature Sensor,

has adjustable setpoint control

and unoccupied override.

Follow the instructions

included with the sensor and

the wiring diagram to install.

Option RB2A, P/N 223125, Remote User Interface, provides access to all of the same functions that are acces-

sible from the FX06 controller except Test Mode.

Option CL47, Room Dehumidistat, is

shipped separately for field installation. The

relative humidity inputs control reheat opera-

tion. Follow the instructions included with

the control and the wiring diagram to install.

NOTE: Applicable with reheat (Option AU7 or

AU8) only. Not available with Option D12F.

FIGURE 51 - Optional Space Mounted Accessories with Option D12 Digital Controls

8.3.3 Optional Space Mounted Accessories for D12 Control Options

8.4 Ignition System

- Models PDH,

SDH, and SHH

The gas-fired furnace is equipped with a direct spark integrated control module (circuit

board). The module monitors the safety devices and controls the operation of the ven-

ter motor and the gas valve between heat cycles. The module in Paragraph 8.4.1 is

used on all of the gas fired models. Depending on control option selected, Model SHH

uses either the control board in Paragraph 8.4.1 or 8.4.2.

8.4.1 Ignition Control

Module used in all

gas control options

EXCEPT Option AG58

and D12G

IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit of a unit with

this ignition controller, place the meter’s test leads into the 5 and 9 pin connectors

located on the ignition control. Do not remove connectors or terminals from the elec-

trical components. Doing so can result in misinterpreted readings due to the ignition

control board’s fault mode monitoring circuits.