beautypg.com

0 controls and operation (cont’d) – Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 60

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 60

1) Call for Heat - The heating/cooling system controller calls for heat. The ignition sys-

tem circuit board checks to see that the limit switch is closed and the pressure switch is

open. If the limit switch is open, the circuit board responds as defined in the “Abnormal

Heat Cycle, Limit Switch Operation”. If the pressure switch is closed, the circuit board

will do four flashes on the green LED and wait indefinitely for the pressure switch to

open. If the pressure switch is open, the circuit board proceeds to prepurge.
2) Prepurge - The circuit board energizes the venter motor and waits for the pressure

switch to close. If the pressure switch does not close within 30 seconds of the venter

motor energizing, the circuit board will do two flashes on the green LED. The circuit

board will leave the venter motor energized indefinitely as long as the call for heat

remains and the pressure switch is open.

When the pressure switch is proven closed, the circuit board begins the prepurge time.

If flame is present any time while in prepurge, the prepurge time is restarted. If flame is

present long enough to cause lockout, the circuit board responds as defined in “Fault

Modes, Undesired Flame”.

The ignition system circuit board runs the venter motor for a 20 second prepurge time,

then proceeds to the ignition trial period.
3) Ignition Trial Period - The ignition system circuit board energizes the spark and

main gas valve. The venter remains energized. If flame is sensed during the first 16

seconds, the spark is de-energized. If flame has not been sensed during the first 16

seconds, the control de-energizes the spark output and keeps the gas valve energized

for an additional one second flame proving period. If flame is not present after the

flame proving period, the control de-energizes the gas valve and proceeds with ignition

re-tries as specified in “Abnormal Heat Cycle, Ignition Retry”. If flame is present, the

circuit board proceeds to steady heat.
4) Steady Heat - Circuit board inputs are continuously monitored to ensure limit and

pressure switches are closed, flame is established (sensor on both burner sections),

and the system controller call for heat remains. When the call for heat is removed, the

ignition system circuit board de-energizes the gas valve and begins postpurge timing.
5) Post Purge - The venter motor output remains on for a 45 second postpurge period

after the system controller is satisfied.

Normal Heat Cycle Operating Sequence with Controller in FIGURE 52.

NOTE: Abnormal Heat

Cycle Functions and

Ignition System Fault

Models for this ignition

controller are explained

in the Operation/

Maintenance/Service

Manual, Form O-PREEVA

& SHH

8.4.2 Ignition Control

Module used in Deep

Modulation Control

Options AG58 and

D12G - Model SHH only

Integrated Control Module for Gas Control Options AG58 and D12G -

The con-

trol module is located in the control compartment with an additional board to

control spark that is attached to the removable shield on the end of the burner.

8.4 Ignition System

- Models PDH,

SDH, and SHH

(cont’d)

8.0 Controls and Operation (cont’d)

Control Status - Green LED Codes

Steady ON ... Normal Operation, No call for heat

Fast Flash .... Normal Operation, Call for heat

1 Flash ......... System Lockout, Failed to detect or sustain

flame

2 Flashes ..... Pressure switch did not close within 30

seconds of venter motor

3 Flashes ..... High limit switch open

4 Flashes ..... Pressure switch is closed before venter

motor is energized

Steady OFF . Blown Fuse, No Power, or Defective Board

Flame Status - Yellow LED Codes

Steady ON ... Flame is sensed

Slow Flash ... Weak flame (current below 1.0 microamps

±50%)

Fast Flash .... Undesired Flame (valve open and no call

for heat)

FIGURE 52 – Ignition Control Module (circuit board)

Spark

Transformer

Control

Plug

Fuse

Thermostat

Connections

Status

Lights

x

LED Lights

See NOTE

below.

NOTE: Set “blower off” dip switch setting to 45 seconds for makeup air application. Refer to the table

on the module for the appropriate settings.

Dip Switch Table