0 mechanical (cont’d), High altitude capacity changes, Form i-pdh/sdh/peh/shh/pxh, page 18 – Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual
Page 18

Form I-PDH/SDH/PEH/SHH/PXH, Page 18
CAUTION: DO NOT
bottom out the gas
valve regulator
adjusting screw.
This can result
in unregulated
manifold pressure
causing excess
overfire and heat
exchanger failure.
High Altitude Capacity
Changes
The input and/or the capacity of the heater changes with altitude.
TABLE 11A lists inputs and capacities at altitudes from sea level to 9,000 ft (2745M)
for Models PDH and SDH installed in the U.S. and to 4,500 ft (1373M) for Canadian
installations.
TABLE 11B lists inputs and capacities for Model SHH.
TABLE 11A - BTUH Inputs and Capacities by Altitude for Models PDH and SDH
Instructions for High Altitude Derate (cont’d)
6.0 Mechanical
(cont’d)
6.1 Gas Heat
Section Piping
and Pressure
- Models PDH,
SDH, and SHH
(cont’d)
3. Single-Stage and Two-Stage High Fire Adjustment - Turn the knob or switch on
the top of the valve to “ON”. Remove the cap from the pressure adjusting screw
and adjust the outlet pressure to the full rate pressure selected from
TABLE 10.
Two Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas valve
and check low fire pressure. To adjust, turn the low pressure regulator screw to
achieve the “2-Stage Low Fire” pressure listed
for the applicable gas control
(TABLE 10). Re-connect the wire to the gas valve.
Electronic Modulation Options AG40, DG2, DG6, and D12B - The electronic
modulation valve itself has no high fire adjustment. The only adjustment on the
modulation valve is the low-pressure bypass setting which is factory set and does
not require field adjustment for high altitude operation.
However, if the elevation on the rating plate does not match the elevation of the
installation, a full rate adjustment is required at the outlet of the combination valve.
To make the full rate adjustment, adjust the outlet pressure of the combination gas
valve when the modulating valve is fully open (there must be a minimum of a 20
VDC signal at the electronic modulating valve to ensure that it is fully open). Set
the outlet pressure of the combination valve to the pressure shown in
TABLE 10.
4. Turn up the thermostat. (NOTE: On Model SDH and SHH, depress and hold the
door safety switch.) Cycle the burner once or twice to properly seat the adjustment
spring in the valve.
Re-check the pressure(s). When the outlet pressure(s) is right for the installation,
remove the manometer and replace the cap. Check for leak at the pressure tap fit-
ting.
5. With the heater operating, determine that the inlet (supply) pressure to the heater
for natural gas is between 5 inches w.c.
(or as noted on the rating plate) and
14 inches w.c. and for propane between 11 and 14 inches w.c. Take this reading
as close as possible to the heater. (Heaters are equipped with a gas valve that
has an inlet pressure tap.) If the inlet (supply) pressure is not within the specified
range, the inlet (supply) pressure must be corrected and Steps 3 and 4 repeated.
6. Find the High Altitude Adjustment label in the literature bag that contained these
instructions. Using a permanent marker, fill-in the appropriate information from
TABLE 11A or 11B. Affix the label to a clean, dry, and conspicuous location on the
outside of the heater access panel.
ALTITUDE
Normal
Input
Thermal
Output
Capacity
2-Stage
Minimum
Input
(applies to
AG2, AG3,
AG15,
AG16)
2-Stage with Venter
Motor Controller
Minimum Input
(applies to AG60,
AG61, AG62, DG1,
DG5, D12C)
Modulation
Minimum Input
(applies to Options
AG8, AG9, AG9H,
AG40, DG2, DG6,
D12B)
Normal
Input
Thermal
Output
Capacity
2-Stage
Minimum
Input
(applies
to AG2,
AG3, AG15,
AG16)
2-Stage with Venter
Motor Controller
Minimum Input
(applies to AG60,
AG61, AG62, DG1,
DG5, D12C)
Modulation
Minimum Input
(applies to Options
AG8, AG9, AG9H,
AG40, DG2, DG6,
D12B)
Normal
Input
Thermal
Output
Capacity
2-Stage
Minimum
Input
(applies to
AG2, AG3,
AG15,
AG16)
2-Stage with Venter
Motor Controller
Minimum Input
(applies to AG60,
AG61, AG62, DG1,
DG5, D12C)
Modulation
Minimum Input
(applies to Options
AG8, AG9, AG9H,
AG40, DG2, DG6,
D12B)
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Feet
Meters
Size 75
Size 100
Size 125
0-2000
0-610
75,000
60,750
52,500
24,750
30,000
18,750
30,000
100,000
81,000
70,000
33,000
40,000
25,000
40,000
125,000
101,250
87,500
41,250
50,000
31,250
50,000
2001-3000
611-915
70,500
57,105
49,350
23,265
28,200
17,625
28,200
94,000
76,140
65,800
31,020
37,600
23,500
37,600
117,500
95,175
82,250
38,775
47,000
29,375
47,000
3001-4000
916-1220
69,000
55,890
48,300
22,770
27,600
17,250
27,600
92,000
74,520
64,400
30,360
36,800
23,000
36,800
115,000
93,150
80,500
37,950
46,000
28,750
46,000
4001-5000
1221-1525
67,500
54,675
47,250
22,275
27,000
16,875
27,000
90,000
72,900
63,000
29,700
36,000
22,500
36,000
112,500
91,125
78,750
37,125
45,000
28,125
45,000
5001-6000
1526-1830
66,000
53,460
46,200
21,780
26,400
16,500
26,400
88,000
71,280
61,600
29,040
35,200
22,000
35,200
110,000
89,100
77,000
36,300
44,000
27,500
44,000
6001-7000
1831-2135
64,500
52,245
45,150
21,285
25,800
16,125
25,800
86,000
69,660
60,200
28,380
34,400
21,500
34,400
107,500
87,075
75,250
35,475
43,000
26,875
43,000
7001-8000
2136-2440
63,000
51,030
44,100
20,790
25,200
15,750
25,200
84,000
68,040
58,800
27,720
33,600
21,000
33,600
105,000
85,050
73,500
34,650
42,000
26,250
42,000
8001-9000
2441-2745
61,500
49,815
43,050
20,295
24,600
15,375
24,600
82,000
66,420
57,400
27,060
32,800
20,500
32,800
102,500
83,025
71,750
33,825
41,000
25,625
41,000
Feet
Meters
Size 150
Size 175
Size 200
0-2000
0-610
150,000
121,500
105,000
49,500
60,000
37,500
60,000
175,000
141,750
122,500
57,750
70,000
43,750
70,000
200,000
162,000
140,000
66,000
80,000
50,000
80,000
2001-3000
611-915
141,000
114,210
98,700
46,530
56,400
35,250
56,400
164,500
133,245
115,150
54,285
65,800
41,125
65,800
188,000
152,280
131,600
62,040
75,200
47,000
75,200
3001-4000
916-1220
138,000
111,780
96,600
45,540
55,200
34,500
55,200
161,000
130,410
112,700
53,130
64,400
40,250
64,400
184,000
149,040
128,800
60,720
73,600
46,000
73,600
4001-5000
1221-1525
135,000
109,350
94,500
44,550
54,000
33,750
54,000
157,500
127,575
110,250
51,975
63,000
39,375
63,000
180,000
145,800
126,000
59,400
72,000
45,000
72,000
5001-6000
1526-1830
132,000
106,920
92,400
43,560
52,800
33,000
52,800
154,000
124,740
107,800
50,820
61,600
38,500
61,600
176,000
142,560
123,200
58,080
70,400
44,000
70,400
6001-7000
1831-2135
129,000
104,490
90,300
42,570
51,600
32,250
51,600
150,500
121,905
105,350
49,665
60,200
37,625
60,200
172,000
139,320
120,400
56,760
68,800
43,000
68,800
7001-8000
2136-2440
126,000
102,060
88,200
41,580
50,400
31,500
50,400
147,000
119,070
102,900
48,510
58,800
36,750
58,800
168,000
136,080
117,600
55,440
67,200
42,000
67,200
8001-9000
2441-2745
123,000
99,630
86,100
40,590
49,200
30,750
49,200
143,500
116,235
100,450
47,355
57,400
35,875
57,400
164,000
132,840
114,800
54,120
65,600
41,000
65,600