beautypg.com

0 controls and operation – Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 51

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 51

8.0 Controls and

Operation

8.1 Gas Controls - apply to Models PDH, SDH, and SHH

All gas-fired furnaces are equipped with a 24-volt combination valve which includes

the automatic electric on-off valve the pressure regulator, the safety pilot valve, and

the manual shutoff valve. Valve on/off function is controlled by the room thermostat or

digital controller.

8.2 Analog Controls

for Heating or

Heating/Makeup

Air

8.2.2 Two-Stage

Operation -

Recirculated Heating

Only (Option AG2

applies to Models

PDH, SDH, and SHH;

Option EG2 applies to

Model PEH)

FIGURE 43 - Unit-mounted

Ductstat, P/N 211481, in

Options AG3 and AG60
Factory

set at

70°F

FIGURE 44 - Remote Temperature Selector, Stage-Adder Module,

and Optional Display Module for Ductstat Control in Two-Stage

Makeup Air Control Options (Option AG15, AG16, AG61, and AG62)

(A) Temperature Selector,

P/N 115848;

(B) Stage Adder,

P/N 115849;

(C) Display Module,

P/N 115852

(A)

(B)

(C)

8.2.3 Two-Stage

Operation - Makeup

Air Heating Only

Application (Option

AG3, AG15, or AG16)

- applies to Models

PDH, SDH, and SHH

Two-stage makeup air units are equipped with a two-stage gas valve, but instead of

control from a two-stage room thermostat, the outlet air temperature is monitored and

controlled by a two-stage ductstat. When the discharge air temperature drops to the

setpoint, factory-set low fire is energized. If low fire (70%) cannot satisfy the ductstat

setting, high fire (100%) is energized.

A makeup air application is usually adjusted to discharge an outlet air temperature

between 65°F and 75°F. In all applications, the allowable temperature rise of the fur-

nace in the installation dictates the limits of the ductstat temperature setting.

Depending on the option selected, the factory-installed sensor is either field-connected

by capillary tubing to the unit-mounted ductstat (

FIGURE 43) or electrically connected

to a remote electronic temperature selector (

FIGURE 44). The remote temperature

selector with stage adder is available with or without a display module.

On gas-fired Models PDH, SDH, and SHH, a two-stage combination gas control valve

provides for low fire (70%) or high fire (100%) operation controlled by a two-stage ther-

mostat. First stage (low fire) is factory set. Both high and low stages are controlled by

a Servo regulator, maintaining constant gas input under wide variations in gas supply

pressure. See instructions packed with the unit for specific gas valve specifications,

wiring, and operating instructions.

On electric heat Model PEH, staging of heat from the heating elements is controlled by

the two-stage thermostat.

A two-stage thermostat is supplied as an option or may be field supplied. Follow the

manufacturer’s instructions and the wiring diagram.

8.2.1 Single-Stage Operation - Recirculated Heating Only (Option

AG1 applies to Models PDH, SDH, and SHH; Option EG1 applies to

Model PEH)

The single-stage gas valve on Model PDH, SDH, or SHH allows for single-stage con-

trol from a single-stage, 24-volt thermostat. On Model PEH, the heating elements are

controlled by a single-stage, 24-volt thermostat. The thermostat is either provided as

an option or field supplied. Follow the thermostat manufacturer’s instructions for instal-

lation. Make wire connections according to the wiring diagram.

WARNING

The operating valve is the prime safety shutoff. All gas supply lines must be free

of dirt or scale before connecting the unit to ensure positive closure. See Hazard

Levels, page 2.

Optional Unit-Mounted Ductstat with Capillary Tubing (Option AG3) - The control

illustrated in

FIGURE 43 has an adjustable range from 50° to 120°F with a fixed differ-