5.0 Suspension
and Mounting
TABLE 5 - Weights
(lbs and kg) of Basic
System and Factory-
Installed Optional
Modules
5.1 Weights
Before installing, check the support structure to be sure that it has sufficient load-bear-
ing capacity to support the weight of unit during installation and operation. Suspension
or mounting is the responsibility of the installer.
TABLE 6 - Corner
Weights of Heat Module
and Blower Section
only for Models Listed
control side
Important NOTES: If controls are on the right side, switch left and right side weights.
Weights do not include the blower motor or any optional modules.
FIGURE 3 - Corner
Weight Locations
Model PDH and Model SDH (gas-fired heat)
75
100
125
150
175 200 225
250
300
350
400A
Model PEH (electric heat)
10A, 20A, 40A 15B, 30B, 60B
N/A
30D, 60D, 90D, 120D
40E, 80E, 120E
Model SHH (high efficiency gas-fired heat)
N/A
130 180
---
260
--
350
--
Model PXH (no heat)
000A
000B
000C
000D
000E
Approximate Net Weights - lbs (does not include motor weight)
Basic Gas Heat & Blower Section (PDH or SDH)
323
331
413
421
478 492 492
615
629
721
732
Basic Electric Heat & Blower Section (PEH)
296
368
N/A
523
594
Basic High Efficiency Gas Heat & Blwr Sctn (SHH)
N/A
538 544
--
729
--
889
--
Blower Section (PXH)
245
307
333
431
483
Approximate Weights (lbs) of factory-attached options (add to weight listed above)
Option AR8, on/off damper (no mixing box)
34
45
56
73
85
Option MXB1
Mixing Box Module
w/o Dampers
2 inlets, single wall
119
132
134
159
174
2 inlets, double wall
146
165
166
199
216
1 inlet, single wall
115
127
130
154
169
1 inlet, double wall
146
166
166
201
219
Cooling Coil
Module with
heaviest coil
weight*
DX coil without
reheat pump
4 row coil
214
252
256
329
365
6 row coil
235
280
284
373
418
DX coil with
reheat pump
4 row coil
331
382
394
494
547
6 row coil
352
410
422
538
600
Chilled water
(filled)
4 row coil
301
363
373
497
559
6 row coil
351
431
441
604
686
Evaporative
Cooling Module
with dry media
12" media
120
141
136
172
190
with wet media &
3" of water
12" media
262
263
218
279
272
Hot Water Heat Module - for PXH with
HW2 only (does not include water wt)
w/4 row,
14 fpi coil
145
175
177
236
263
Approximate Net Weights - kg (does not include motor weight)
Basic Gas Heat & Blower Section (PDH or SDH)
147
150
187
191
217
223
223
279
285
327
332
Basic Electric Heat & Blower Section (PEH)
134
167
N/A
237
269
Basic High Efficiency Gas Heat & Blwr Sctn (SHH)
N/A
244
247
--
331
--
403
--
Blower Section (PXH)
111
139
151
195
219
Approximate Weights (kg) of factory-attached options (add to weight listed above)
Option AR8, on/off damper (no mixing box)
15
20
25
33
39
Option MXB1 Mixing
Box Module w/o
Dampers
2 inlets, single wall
54
60
61
72
79
2 inlets, double wall
66
75
75
90
95
1 inlet, single wall
52
58
59
70
77
1 inlet, double wall
66
75
75
91
99
Cooling Coil Module
with heaviest coil
weight*
DX coil without
reheat pump
4 row coil
97
114
116
149
166
6 row coil
107
127
129
169
190
DX coil with reheat
pump
4 row coil
150
173
179
224
248
6 row coil
160
186
191
244
272
Chilled water (filled)
4 row coil
137
165
169
225
254
6 row coil
159
195
200
274
311
Evaporative Cooling
Module
with dry media
12" media
54
64
62
78
86
with wet media &
76mm of water
12" media
119
119
99
127
123
Hot Water Heat Module - for PXH with
HW2 only (does not include water weight)
w/4 row,
14 fpi coil
66
79
80
107
119
* Cooling coil cabinet
module weight is
estimated for heaviest
coil. If more accurate
information is needed,
check with your
distributor or Reznor
®
Representative who
either has the specific
information in the order
specifications or has
software to generate the
information.
5.2 Lifting and
Suspension
The heavy gauge base of the unit has forklift openings in both sides. See
FIGURE
4. Use these openings to move and lift the unit. (NOTE: If system has more than two
optional modules, check for labels identifying which side to lift.) Braces underneath are
spaced to accommodate a minimum fork length of 24” (610mm).
In addition, the base of all units has a lifting hole at each corner. Systems with a mixing
box and/or a cooling cabinet have additional side suspension points. When lifting, lift
from all of the suspension points on the unit (4, 6, or 8). Use spreader bars to lift the
unit straight up with vertical force only.
Top View
SHH
130
180
260
350
Corner
(FIG 3)
Approx Wt (lbs) - Heat
Section & Blower only
LR
81
82
127
188
RR
87
88
144
192
RF
193
193
241
264
LF
180
180
217
245
Corner
(FIG 3)
Approx Wt (kg) - Heat
Section & Blower only
LR
37
37
58
85
RR
39
40
65
87
RF
88
88
109
120
LF
82
82
98
120
PEH
10A, 20A, 40A
15B, 30B, 60B
30D, 60D, 90D, 120D
40E, 80E, 120E
Approx Wt of
Each Corner
lbs
kg
lbs
kg
lbs
kg
lbs
kg
74
34
92
42
131
59
149
68
PDH/SDH
75
100 125 150 175 200 225 250 300 350 400A
Corner (FIGURE 3) Approximate Corner Weights (lbs) - Heat Section & Blower only
LR
70
70
92
92
80
80
80
124 124 158
158
RR
63
63
87
87
74
74
74
110 110 155
155
RF
92
96
113 117 156 163 163 180 187 198
202
LF
98
102 121 125 168 175 175 201 208 210
217
Corner (FIGURE 3) Approximate Corner Weights (kg) - Heat Section & Blower only
LR
32
32
42
42
36
36
36
56
56
72
72
RR
29
29
39
39
34
34
34
50
50
70
70
RF
42
44
51
53
71
74
74
82
85
90
92
LF
44
46
55
57
76
79
79
91
94
95
98