beautypg.com

Reznor SHH (Indoor PreevA) Unit Installation Manual User Manual

Page 15

background image

Form I-PDH/SDH/PEH/SHH/PXH, Page 15

Modulating Valve in

Options AG8, AG9,

AG9H, AG40, DG2,

DG6, and D12B -- DO

NOT adjust.

CAUTION: DO NOT

bottom out the gas

valve regulator

adjusting screw.

This can result

in unregulated

manifold pressure

causing excess

overfire and heat

exchanger failure.

To ensure an accurate high fire

reading at the single-stage valve, a

minimum signal of 20VDC must be

present at the modulating valve.

FIGURE 7 - Top View

of Modulating Valve in

AG8, AG9, AG9H, AG40,

DG2, DG6, and D12B

Normally, when operating at the altitude indicated on the rating plate,

adjustments to the factory settings should not be necessary. If adjustment is

required, remove the cap from the adjustment screw on the single or two-stage valve.

Adjust pressure setting by turning the regulator screw IN (clockwise) to increase

pressure. Turn regulator screw OUT (counterclockwise) to decrease pressure. If

an adjustment is made, turn up the thermostat. Cycle the burner once or twice to

properly seat the adjustment spring in the valve. Re-check the pressure. When the

outlet pressure is right for the installation, remove the manometer and replace the

cap. Check for a leak at the pressure tap fitting.

WARNING

Valve outlet gas pressure must never exceed the value listed in

TABLE 10 (or as shown on the rating plate).

To check low-fire (bypass pressure), locate the 1/4” NPT pressure tap behind the

orifice adapter as shown in

FIGURE 8. Connect a manometer to the 1/4” pressure tap.

FIGURE 8 - Pressure

Tap Location for

Measuring Low Fire

Outlet (Bypass)

Pressure -- Electronic

Modulation Gas Control

Options AG8, AG9,

AG9H, AG40, DG2, DG6,

and D12B

WARNING:

Measure low-fire

pressure at this location only for

units with electronic modulation

gas control Option AG8, AG9,

AG9H, AG40, DG2, DG6, or D12B).

1/4” NPT

Pressure

Tap

2) Measure High Fire Pressure and Adjust (if

needed)

Open the manual valve and operate the heater.

Using the manometer connected to the single-stage

valve, measure the outlet pressure. To ensure an

accurate high-fire gas pressure reading at the single-

stage valve, a minimum 20VDC signal MUST be present

at the modulating gas valve.

Normally, when operating at the altitude indicated

on the rating plate, adjustments to the factory

settings should not be necessary. If adjustment is

required, remove the cap from the adjustment screw

on the single-stage valve. Adjust pressure setting by

turning the regulator screw IN (clockwise) to increase

pressure. Turn regulator screw OUT (counterclockwise)

to decrease pressure. If an adjustment is made, turn up

the thermostat. Cycle the burner once or twice to properly

seat the adjustment spring in the valve. Re-check the

pressure. When the outlet pressure is right for the

installation, remove the manometer and replace the cap.

Check for a leak at the pressure tap fitting.

WARNING

Valve outlet gas pressure must never

exceed the value listed in TABLE 10, page

17, (or as shown on the rating plate).

3) Measure Low Fire (Bypass) Pressure

To measure low-fire (bypass pressure) on electronic

modulation gas control Options AG8, AG9, AG9H, AG40,

DG2, DG6, and D12B, disconnect one of the wire leads

to the modulating valve. Measure the pressure with the

manometer attached to the pressure tap just behind the

orifice adapter (

FIGURE 8). Re-connect the wire.

DO NOT attempt to adjust the bypass (low-fire) pressure.

If bypass pressure is incorrect (see

TABLE 10, page 17),

contact the factory.

CAUTION: DO NOT bottom out the gas valve regulator adjusting screw. This can result in

unregulated manifold pressure causing excess overfire and heat exchanger failure.

INSTRUCTIONS

for ELECTRONIC

MODULATION Gas

Control Options AG8,

AG9, AG9H, AG40, DG2,

DG6, and D12B

1) Gas Valve and Manifold Pressure Tap Locations

The manifold includes a single-stage valve and a modulating valve (

FIGURE 7).

Locate the outlet pressure tap just behind the orifice adapter (See

FIGURE 6). To

check high fire outlet pressure, connect a manometer to the outlet pressure tap just

behind the orifice adapter.