Analysis tab – Rockwell Automation Motion Analyzer Software User Manual
Page 48

48
Rockwell Automation Publication MOTION-UM004B-EN-P - October 2012
Chapter 1
Welcome to Motion Analyzer Software
1.2.2.4.3.3. Analysis Tab
Click Analysis to display plots of drive module activity in terms of the DC bus
voltage and DC bus current:
• The red line is the bus voltage trip point.
• The green line is the DC bus voltage.
• The grey line is the bus current.
Figure 36 - Analysis Tab Dialog Box
Table 30 - Analysis Tab Properties
Parameters
Description
Simulation Parameters
(1)
)
Shunt On
The voltage level where the shunt enables.
Shunt Off
The voltage level where the shunt turns off.
Trip
The voltage level where the drive trips on an overvoltage fault by changing the trip volts.
Resistance
The shunt resistance level in ohms.
Power
Changing the power value modifies how much energy the shunt resistor can dissipate continuously.
Capacitance
Changing the capacitance value changes the DC bus capacitance.
)
Time From/
Voltage From
Check these boxes to adjust the X- and Y-axis values for the plot. Click Plot to implement these changes.
Time Slice
The Time Slice variable sets the time interval for the Analysis tab. Because the shunt switching action is modeled
during selection, this value needs to be very short to obtain an accurate shunt selection (0.1 ms, for example).
However, if the total cycle time is more than a few seconds, the calculation time may become excessive. The time is
equal to the longest axis cycle.
(1) Click Apply to implement these changes.