Understanding Your System Solution

Chapter 3

Figure 196 - Controlled Stop Details Dialog Box

Table 147 - Controlled Stop Details Properties (refer to

Figure 196

)

Parameters

Description

Decel Distance

This is the critical deceleration distance. It is common to find that the mechanical design does
not allow enough distance to stop, if a fault occurs at the end of normal travel. This display
helps to predict the required distances on both the motor side and the load side.

Decel Time

The time required to come to a complete stop.

Amplifier Utilization

This mimics the internal drive protection algorithm. In the event that 100% is exceeded, the
drive faults and the motor coasts to a stop.

Energy Absorbed

This is an indication of the energy that must be handled during a controlled stop and may help
to size dump resistors.

IMPORTANT

Amplifier utilization is critical because it may indicate that a bigger drive is
necessary to achieve the required stopping time and/or distance.