The parameters listed in this section may or may not apply to your application. Refer to
the WebPak 3000 software manual (D2-3444) for more information about each of
these parameters.

13.1 Analog Outputs

The Regulator board provides two analog outputs that are unfiltered or filtered. The
I/O Expansion board has two unfiltered analog outputs,

ANLG

OUT

3 and 4. One can

generate a bipolar DC voltage only. The other can be configured to generate a DC
voltage from a 0 to +/-10 VDC, 4 to 20 mA, or 10 to 50 mA signal.

These outputs can be scaled to generate DC voltage signals as low as 5 V, but
maximum resolution (0.025%) is obtained when the full scale output signal is used.
The full scale value (FSV) is determined based on the selected parameter group: load,
speed, voltage, power, field, or other.

Analog outputs are read every 10 ms.

Use This Chapter for These Applications:

Constant Diameter Speed Regulator

Variable Diameter Speed Regulator

Constant Diameter Current Regulator

Variable Diameter Current Regulator

Constant Diameter Position Regulator

Variable Diameter Position Regulator

Constant Diameter Tension Regulator

Variable Diameter Tension Regulator