Configuring Other Parameters
13-1
C
HAPTER
13
Configuring Other Parameters
The parameters listed in this section may or may not apply to your application. Refer to
the WebPak 3000 software manual (D2-3444) for more information about each of
these parameters.
13.1 Analog Outputs
The Regulator board provides two analog outputs that are unfiltered or filtered. The
I/O Expansion board has two unfiltered analog outputs,
ANLG
OUT
3 and 4. One can
generate a bipolar DC voltage only. The other can be configured to generate a DC
voltage from a 0 to +/-10 VDC, 4 to 20 mA, or 10 to 50 mA signal.
These outputs can be scaled to generate DC voltage signals as low as 5 V, but
maximum resolution (0.025%) is obtained when the full scale output signal is used.
The full scale value (FSV) is determined based on the selected parameter group: load,
speed, voltage, power, field, or other.
Analog outputs are read every 10 ms.