Configuring the Speed Loop
3-5
þ
To configure the speed reference ramp:
▲
Set
TRIM
MODE
SELECT
(P.110). The choices are:
NO
TRIM
- Used when the drive is configured as:
•
a stand-alone speed-regulated section
•
a lead or master section of a process
•
an inner speed loop as part of major outer control loop design.
INCREMENTAL
- Depending on the polarity of the trim reference, adds or
subtracts from the speed reference a constant value that is derived from
TOP
LINE
SPEED
(P.020).
PROPORTIONAL
- Depending on the polarity of the trim reference, adds or
subtracts from the speed reference a value that varies based on the speed
reference value, as determined by
SPD
SOURCE
SELECT
OUT
(P.193).
The actual value of the signal used to trim the selected speed loop signal, after it is set
by a multiplier block, is defined as
TRIM
OUTPUT
(P.197). This is summed with
SPD
SOURCE
SELECT
OUT
(P.193) to become the input to the
LIMIT
block.
3.2.1 The LIMIT Block
The
LIMIT
block limits the amplitude of the line speed reference. The input to this block
is the sum of
TRIM
OUTPUT
(P.197) and
SPD
SOURCE
SELECT
OUT
(P.193). For variable
diameter applications, the minimum and maximum line speed limits are determined
from
NORM
ROLL
DIAMETER
(P.131) and the motor minimum and maximum limits
(
MINIMUM
SPEED
(P.003) and
MAXIMUM
SPEED
(P.004)).
Refer to figure A.5 in Appendix A of the software manual (D2-3444) as you set up the
LIMIT
block.
þ
To set up the
LIMIT
block:
▲
Set
MINIMUM
SPEED
BYPASS
(P.111). The choices are:
ON
- Allows the drive to operate down to zero speed.
OFF
- (Default) Establishes the low end of the
LIMIT
block to a value determined
by the section diameter.
þ
If this is a constant diameter application:
▲
Set
DIAMETER
CALC
ENABLE
(P.826) to
DISABLE
.
Range:
NO
TRIM
,
INCREMENTAL
,
PROPORTIONAL
P.110 =
Range:
ON
,
OFF
P.111 =
!
ATTENTION: The drive can operate at and maintain zero speed when
MINIMUM
SPEED
BYPASS
(P.111) is set to
ON
. The user is responsible for
assuring safe conditions for operating personnel by providing suitable
guards, audible or visual alarms, or other devices to indicate that the
drive is operating at or near zero speed. Failure to observe this precaution
could result in severe bodily injury or loss of life.
Range:
ENABLE
,
DISABLE
P.826 =