Configuring the Speed Loop

3-5

þ

To configure the speed reference ramp:

Set

TRIM

MODE

SELECT

(P.110). The choices are:

NO

TRIM

- Used when the drive is configured as:

a stand-alone speed-regulated section

a lead or master section of a process

an inner speed loop as part of major outer control loop design.

INCREMENTAL

- Depending on the polarity of the trim reference, adds or

subtracts from the speed reference a constant value that is derived from

TOP

LINE

SPEED

(P.020).

PROPORTIONAL

- Depending on the polarity of the trim reference, adds or

subtracts from the speed reference a value that varies based on the speed
reference value, as determined by

SPD

SOURCE

SELECT

OUT

(P.193).

The actual value of the signal used to trim the selected speed loop signal, after it is set
by a multiplier block, is defined as

TRIM

OUTPUT

(P.197). This is summed with

SPD

SOURCE

SELECT

OUT

(P.193) to become the input to the

LIMIT

block.

3.2.1 The LIMIT Block

The

LIMIT

block limits the amplitude of the line speed reference. The input to this block

is the sum of

TRIM

OUTPUT

(P.197) and

SPD

SOURCE

SELECT

OUT

(P.193). For variable

diameter applications, the minimum and maximum line speed limits are determined
from

NORM

ROLL

DIAMETER

(P.131) and the motor minimum and maximum limits

(

MINIMUM

SPEED

(P.003) and

MAXIMUM

SPEED

(P.004)).

Refer to figure A.5 in Appendix A of the software manual (D2-3444) as you set up the

LIMIT

block.

þ

To set up the

LIMIT

block:

Set

MINIMUM

SPEED

BYPASS

(P.111). The choices are:

ON

- Allows the drive to operate down to zero speed.

OFF

- (Default) Establishes the low end of the

LIMIT

block to a value determined

by the section diameter.

þ

If this is a constant diameter application:

Set

DIAMETER

CALC

ENABLE

(P.826) to

DISABLE

.

Range:

NO

TRIM

,

INCREMENTAL

,

PROPORTIONAL

P.110 =

Range:

ON

,

OFF

P.111 =

!

ATTENTION: The drive can operate at and maintain zero speed when

MINIMUM

SPEED

BYPASS

(P.111) is set to

ON

. The user is responsible for

assuring safe conditions for operating personnel by providing suitable
guards, audible or visual alarms, or other devices to indicate that the
drive is operating at or near zero speed. Failure to observe this precaution
could result in severe bodily injury or loss of life.

Range:

ENABLE

,

DISABLE

P.826 =