Rockwell Automation WebPak 3000 DC Drive Application Workbook Version 1.1 User Manual
Page 33
Configuring the Current Minor Loop
4-5
▲
Set or verify
CT
TURNS
RATIO
(P.010).
J
18
ARM
I
FB
RESISTOR
(P.395) indicates the burden resistor position required to
properly scale armature current feedback.
▲
Set
INV
FAULT
AVOID
SEL
(P.312) to specify how the drive responds to an
inverting fault. Refer to the WebPak 3000 software manual (D2-3444) before
setting this parameter.
The following parameters are set by the current minor loop self-tuning function.
Self-tuning will overwrite values entered manually.
▲
Set
CML
PI
PROP
GAIN
(P.301).
▲
Set
CML
PI
LEAD
FREQUENCY
(P.302).
!
ATTENTION: The
CT
TURNS
RATIO
(P.010) parameter is used in the
calculation of the burden resistor value. Do not change this parameter
from its factory default value unless you are replacing the Regulator
board. Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Range:
FACTORY
SET
;
SEE
SOFTWARE
MANUAL
(D2-3444)
P.010 =
Range:
DISABLED
,
FAULT
IMMEDIATELY
,
DELAY
BEFORE
FAULT
P.312 =
!
ATTENTION: When activated, inverting fault avoidance takes control of
the current minor loop by either forcing the current reference to zero (if
the drive is regenerating) or by disabling the regenerative bridge (if the
drive is not regenerating). It is the user’s responsibility to analyze the
application to determine whether or not inverting avoidance should be
used. Failure to observe this precaution could result in bodily injury.
Range: 0.000 to 4.000
P.301 =
Range: 10 to 500
RAD
/
S
P.302 =
RAD
/
S