Configuring the Tension Outer Control Loop

12-1

C

HAPTER

12

Configuring the Tension

Outer Control Loop

The tension outer control loop regulator uses the same

RATELIM

and

PI

control blocks

as the current major outer control loop.

The tension output control loop includes:

Tension

PI

input

Tension

PI

limits

Tension

PI

output

þ

To select the tension outer control loop:

Set

OCL

SELECT

(P.817) to

TENSION

.

12.1 The Tension PI Input

Refer to figure A.18 in Appendix A of the software manual (D2-3444) as you configure
the tension

PI

input.

The input to the

PI

block is the rate-limited value of

TENSION

DEMAND

(P.844), which is

the input to

RATELIM

block. The output is

TEN

RAMP

OUTPUT

(P.842).

þ

To configure the

PI

block input:

Set

TEN

RAMP

TIME

(P.833) to specify the reference rate of change.

Connect the analog tension feedback signal to terminals 52(+) and 53(-) on
the I/O Expansion board.

The standard

PI

block feedback is an analog signal proportional to tension;

therefore, it is assumed that the tension transducer output has been amplified
(if necessary) and conditioned to provide a 0 to 10 volt

DC

signal linear from 0

to maximum tension.

Use This Chapter for These Applications:

Constant Diameter Tension Regulator

Variable Diameter Tension Regulator

Generic

Range:

NONE

,

TENSION

,

CURRENT

,

POSITION

P.817 =

7(16,21

Range: 0.1 to 60.0

SECONDS

P.833 =

SECONDS