Configuring the Outer Control Loop Reference

9-5

Set

ANLG

OUT

3

SIG

TYPE

(P.419) to 0 to 10 volts or 4 to 20 mA, depending on

the type of input signal the dancer transducer requires.

Set

ANLG

OUT

3

GAIN

ADJ

(P.420) to specify the maximum value of the analog

output when the dancer loading input is at its maximum

.

Range: 0 to 10

V

, +/-10

V

, 4 to 20 mA, 10 to 50 mA

P.419 =

Range: .500 to 1.300

P.420 =

DANCER LOADING SETUP EXAMPLE

Assumptions:

When

TENSION

SETPOINT

(P.854) is set to

MAXIMUM

,

TENSION

DEMAND

(P.844) is at

4095 counts.

When

TENSION

SETPOINT

(P.854) is set to

MINIMUM

,

TENSION

DEMAND

(P.844) is at 0

counts.

The pneumatic transducer uses a 4 to 20 mA input, zero loading (tension) is
equivalent to 4 mA, and maximum loading (tension) is equivalent to 20 mA.

Under these conditions:

Set

MAX

DANCER

LOAD

(P.831) to 4095 counts, where 4095 equals maximum web

tension.

Set

MIN

DANCER

LOAD

(P.832) to 0 counts, where 0 counts equals zero web

tension at 4 mA.