Configuring the Current Major Outer Control Loop
10-1
C
HAPTER
10
Configuring the Current
Major Outer Control Loop
The current major outer control loop uses the same
RATELIM
and
PI
control blocks as
the tension outer control loop.
The current major outer control loop includes the following sections:
•
Gain profiler
•
Tension-to-current scaling
•
Tension
PI
input
•
Tension
PI
limits
•
Tension
PI
output
þ
To select the current major outer control loop (
OCL
):
▲
Set
OCL
SELECT
(P.817) to
CURRENT
.
10.1 Gain Profiler for the Current Major Outer Control
Loop
The profiler block uses equations that are based on the dynamic physical properties of
the connected load to maximize system response and stability. Refer to figure A.19 in
Appendix A of the software manual (D2-3444).
Four inputs to the profiler block are calculated internally:
•
NORM
FIELD
REF
(P.130) is the output of the field current regulator task.
•
NORM
ROLL
DIAMETER
(P.131) is the output of the diameter calculator task.
•
INSTANTANEOUS
INERTIA
(P.230) is the calculated value of the dynamic load inertia as
provided by the inertia compensation task.
Use This Chapter for These Applications:
•
Constant Diameter Current Regulator
•
Variable Diameter Current Regulator
•
Generic
Range:
NONE
,
TENSION
,
CURRENT
,
POSITION
P.817 =
&855(17