Configuring the Current Major Outer Control Loop

10-1

C

HAPTER

10

Configuring the Current

Major Outer Control Loop

The current major outer control loop uses the same

RATELIM

and

PI

control blocks as

the tension outer control loop.

The current major outer control loop includes the following sections:

Gain profiler

Tension-to-current scaling

Tension

PI

input

Tension

PI

limits

Tension

PI

output

þ

To select the current major outer control loop (

OCL

):

Set

OCL

SELECT

(P.817) to

CURRENT

.

10.1 Gain Profiler for the Current Major Outer Control

Loop

The profiler block uses equations that are based on the dynamic physical properties of
the connected load to maximize system response and stability. Refer to figure A.19 in
Appendix A of the software manual (D2-3444).

Four inputs to the profiler block are calculated internally:

NORM

FIELD

REF

(P.130) is the output of the field current regulator task.

NORM

ROLL

DIAMETER

(P.131) is the output of the diameter calculator task.

INSTANTANEOUS

INERTIA

(P.230) is the calculated value of the dynamic load inertia as

provided by the inertia compensation task.

Use This Chapter for These Applications:

Constant Diameter Current Regulator

Variable Diameter Current Regulator

Generic

Range:

NONE

,

TENSION

,

CURRENT

,

POSITION

P.817 =