Refer to the WebPak 3000 software manual (D2-3444) for the
descriptions of the following parameters and adjust them to tune the
field control loop if necessary.

FLD

WEAKEN

THRESHOLD

(P.518).

FLD

WEAKEN

LEAD

FREQ

(P.520).

FLD

WEAKEN

PROP

GAIN

(P.519).

5.4

The Field Regulator

The field current regulator operates closed loop with a

PI

amplifier block.

FIELD

DELTA

(P.588) is the output of the

PI

block and sets the firing angle of the field phase firing

logic which, in turn, sets the voltage output level of the field power bridge.

þ

To modify the lead frequency and gain of the

FIELD

AUTO

WEAKEN

PI

block

(recommended for stable operation of the field current regulator

PI

block):

Set

FIELD

PI

PROP

GAIN

(P.514) to tune for stable operation of the spillover

regulator

PI

block.

Set

FIELD

PI

LEAD

FREQ

(P.515) to tune for stable operation of the spillover

regulator

PI

block.

Range: 0 to 120% of P.009

P.518 =

%

Range: 0.00 to 56.54

RAD

/

S

P.520 =

RAD

/

S

Range: 0.01 to 128.00

P.519 =

Range: 0.10 to 128.00

P.514 =

Range: 0 to 282.70

RAD

/

S

P.515 =

RAD

/

S