8-2

WebPak 3000 DC Drive Application Workbook, Version 1.1

Run the drive as a speed regulator long enough to stabilize the mechanical
characteristics of the load (bearings, couplings, etc.).

Set the speed reference to 10% of

TOP

LINE

SPEED

(P.020).

Run the drive and adjust

FRICTION

LOSS

(P.123) until the speed loop

PI

output

SPD

LOOP

OUTPUT

(P.299) is zero.

Set the speed reference to 100% of

TOP

LINE

SPEED

(P.020).

Run the drive and adjust

WINDAGE

LOSS

(P.243) until

SPD

LOOP

OUTPUT

(P.299)

is zero.

Range: 0.0 to 50.0%

P.123 =

%

Range: 0.0 to 50.0%

P.243 =

%