beautypg.com

Object – Rockwell Automation FactoryTalk Historian SE 4.0 Installation and Configuration Guide User Manual

Page 162

background image

Appendix D FactoryTalk View SE TrendX

162

Rockwell Automation Publication HSE-IN025A-EN-E–September 2013

If you intend to use the FactoryTalk View TrendX display object to

trend data points (tags) from the FactoryTalk Historian SE server,
you need to establish a security connection between the device on
which you use the TrendX object (e.g. a computer with FactoryTalk
View running) and the FactoryTalk Historian SE server. You can
achieve it by creating a trust between the IP address of the device
and the FTHOperator user of the FactoryTalk Historian SE server
security model.

NOTE

For more information on the FactoryTalk Historian SE server users,
see "Historian Security Components and Their Privileges (page 65)".

To create a security trust for the FactoryTalk View TrendX
object:

1. On the computer with the FactoryTalk Historian SE server

installed, go to

Start > All Programs > Rockwell Software >

FactoryTalk Historian SE > System Management Tools. The
System Management Tools dialog box appears.

2. Under Collectives and Servers, select the FactoryTalk

Historian SE server, for which you want to create the trust.

3. Under System Management Tools, select Security >

Mappings & Trust.

4. Go to the Trusts tab.
5. On the toolbar, click the arrow next to

, and select

Advanced.

6. In the Add New Trust dialog box, provide the following

information:

Item name

Description

Trust Name

Type a name of the trust.

Creating Security Trusts for
the FactoryTalk View TrendX
Display Object