Bulletin 290D/291D/294D Programmable Parameters
Chapter 4
Basic Configuration Group
SnapShotLAvgAmps
This parameter provides a snapshot of
average of 3 Phase currents at time
of last trip.
Parameter Number
26
Access Rule
GET
Data Type
INT
Group
Trip Status
Units
x.xx Amps
Minimum Value
0
Maximum Value
32767
Default Value
0
SnapShot%Thermal
This parameter provides a snapshot of the
percentage of Thermal Capacity used at
time of last trip.
Parameter Number
27
Access Rule
GET
Data Type
USINT
Group
Trip Status
Units
Percent
Minimum Value
0
Maximum Value
100
Default Value
0
FLASetting
The motor’s full load current rating is
programmed in this parameter.
Parameter Number
28
Access Rule
GET/SET
Data Type
INT
Group
Basic Configuration
Units
x.xx Amps
Minimum Value
See Table 20.
Maximum Value
Default Value
See Table 20.
Table 20 - FLA Setting Ranges and Default Values (with indicated setting precision)
FLA Current Range (A)
Default Value
460V AC
Minimum Value
Maximum Value
290D/1_-FA_*
3 Hp
0.24
3.5
0.24
290D/1_-FB_*
5 Hp
1.1
7.6
1.1