User i/o configuration group – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 138
![background image](/manuals/578111/138/background.png)
138
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
User I/O Configuration Group
RunNetIdlValue
This parameter determines the state that
starter assumes when the network is idle
and Parameter 47 (RunNetIdlAction) is
set to 1.
0 = OFF
1 = ON
Parameter Number
48
Access Rule
GET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
0x3F
Default Value
0
IOPointConfigure
This parameter determines the point
that is configured:
0 = Input
1 = Output
Parameter Number
49
Access Rule
GET/SET
Data Type
WORD
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
0x3F
Default Value
0
Bit
Function
5
4
3
2
1
0
—
—
—
—
—
X
Pt00
—
—
—
—
X
—
Pt01
—
—
—
X
—
—
Pt02
—
—
X
—
—
—
Pt03
—
X
—
—
—
—
Pt04
X
—
—
—
—
—
Pt05
FilterOffOn
This parameter determines the input
(which must be present for this time)
before being reported ON.
Parameter Number
50
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
msecs
Minimum Value
0
Maximum Value
64
Default Value
0