Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 140
![background image](/manuals/578111/140/background.png)
140
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
OutNetFaultValue
This parameter determines the state that
starter outputs when an Ethernet fault
occurs and Parameter 54
(OutNetFaultState) is set to 0.
0 = OFF
1 = ON
Parameter Number
55
Access Rule
GET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutNetIdleState
This parameter in conjunction with
Parameter 57 (OutNetIdleValue) defines
how the starter outputs will respond when
a network is idle.
0 = GoToIdleValue
1 = HoldLastState
Parameter Number
56
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutNetIdleValue
This parameter determines the state that
starter outputs assumes when the
network is idle and Parameter 56
(OutNetIdleState) is set to 0.
0 = OFF
1 = ON
Parameter Number
57
Access Rule
GET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Input00Function
This parameter determines the special
function for User Input 0:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive.
All others are edge sensitive
Parameter Number
58
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
5
Default Value
0