Advanced configuration – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 143

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
143
Bulletin 290D/291D/294D Programmable Parameters
Chapter 4
Advanced Configuration
KeypadDisable
This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled
Parameter Number
67
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
SetToDefaults
This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults
Parameter Number
68
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
AccelTime2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number
69
Related Parameters
36
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 2
0
0
Time
Decel
Time 2
Ac
celer
ation
Dec
eler
ation