Quick reference troubleshooting, Fault led indications, Bulletin 290d/291d faults – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 170
![background image](/manuals/578111/170/background.png)
170
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 5
Diagnostics
Quick Reference
Troubleshooting
The LEDs on the front of the ArmorStart LT provide an indication as to the
health of the device and network. The following is a brief troubleshooting guide.
Fault LED Indications
The RUN/FLT LED will blink red in a prescribed fault pattern when a
protection fault (trip) condition is present. The LED will blink in 0.5 second
intervals when indicating a fault code. Once the pattern is finished, there will be a
2 second pause after which the pattern will be repeated.
Bulletin 290D/291D Faults
Bulletin 290D/291D faults are detected by the main control board. When the
[ProtFltResetMode] Parameter 41 is set to the value 1=Automatic, the auto
resettable faults in the table will reset automatically when the fault condition is
no longer present.
Table 23 - LED Status Indication
Status LED
Description
Recommended Action
PWR (Control) Status Indicator
Off
The PWR LED is not illuminated at all.
Verify power is connected and with proper polarity.
Green
Voltage is present.
No action
Flashing Yellow
Power has fallen below minimum acceptable level.
Verify that the control power is between 19.2 and 26V DC.
RUN/FLT Status Indicator
Off
The RUN/FLT LED is not illuminated when a Run command has
been issued.
Verify that PLC is in Run mode. Verify that the correct run
bit is being controlled. Verify that a stop condition does
not exist.
Green
Valid start command
No action
Flashing Red
Protection fault
Count flashes and refer to Table 24 and 25.
NS – Network Status Indicator
Off
The NS LED is not illuminated.
Check to make sure the product is properly wired
and configured on the network.
Steady Green
CIP connection is established.
No action
Flashing Green
An IP address is configured, but no CIP connections are
established, and an Exclusive Owner connection has not timed
out.
Check to make sure the product is properly wired
and configured on the network.
Flashing Red
Connection has timed out.
Check to make sure the PLC is operating correctly and that
there are no media/cabling issues. Check to see if other
network devices are in a similar state.
Solid Red
Duplicate IP address detected
Check for node address conflict and resolve.
Flashes
Green-Red
The device has not completed the initialization, is not on an
active network, or has not finished self test at power up.
Remove or change the IP address of the conflicting device.
I/O Status Indicators
Off
The user has plugged into the I/O, but the indicator did not
illuminate, once initiated.
Verify the wiring of Input or Output is correct. When used
as an output point, ensure the corresponding bit in
parameter 49 [IOPointConfiguration] is set to Output.