236
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Appendix B
CIP Information
DeviceNet Interface Object
CLASS CODE 0x00B4
The following class attributes will be supported.
4
Warning 4
—
5
Warning 5
Indicates missing supply phase. This fault can be disabled.
6
Jam Warning
Motor current has exceeded jam warning level.
7
Underload Warning
Motor current dropped below Underload Warning level.
8
Warning 8
—
9
Warning 9
—
10
Warning 10
—
11
Warning 11
—
12
Warning 12
—
13
Switched Pwr Warn
Indicates the control power has dipped below 19 Volts.
Not available in units with Integrated Power Supply.
14
Under Power Warn
Indicates the internal power supply is below its optimal level.
Available in units with Integrated Power Supply only.
15
Warning 15
—
16
Warning 16
—
17
Warning 17
—
18
Warning 18
—
19
Warning 19
—
20
Warning 20
—
21
Aux Power Warn
Indicates auxiliary Power was has dipped below 19 Volts.
Not available in units with Integrated Power Supply.
22
Warning 22
…
31
FanRPMWarning
Internal fan is too slow, or needed to be kick started
…
41
BrakeConfig
Values for params 58 - 63 and/or param 49 are invalid
42
IOPointConfig
Values for params 58 - 63 and/or param 49 are invalid
43
ZIPConfig
Values for params 114 - 129 result in ZIP data mapping overlap
44
JamConfig
Param 72 JamTripLevel is less than Param 73 JamWarningLevel
45
UnderloadConfig
Param 78 ULTripLevel is greater than Param 79 ULWarningLevel
…
75
Warning 75
Table 32 - Fault Codes, Fault Text, and Fault Help Strings for ArmorStart LT
Warning
Code
Warning Text
Help Text
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
2