beautypg.com

Advanced configuration – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 106

background image

106

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

Advanced Configuration

KeypadDisable

This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled

Parameter Number

67

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

SetToDefaults

This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults

Parameter Number

68

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OLWarningLevel

This parameter determines the Overload
Warning Level in % Thermal Capacity Used
(%TCU).

Parameter Number

69

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

%TCU

Minimum Value

0

Maximum Value

100

Default Value

85

JamInhibitTime

This parameter determines the time
during motor starting that Jam detection
is inhibited.

Parameter Number

70

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs.

Minimum Value

0

Maximum Value

250

Default Value

10