Advanced configuration – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 106
106
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
Advanced Configuration
KeypadDisable
This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled
Parameter Number
67
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
SetToDefaults
This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults
Parameter Number
68
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OLWarningLevel
This parameter determines the Overload
Warning Level in % Thermal Capacity Used
(%TCU).
Parameter Number
69
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
%TCU
Minimum Value
0
Maximum Value
100
Default Value
85
JamInhibitTime
This parameter determines the time
during motor starting that Jam detection
is inhibited.
Parameter Number
70
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs.
Minimum Value
0
Maximum Value
250
Default Value
10