Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 178

178
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 6
Specifications
Environmental Ratings
Operating Temperature Range
-20…+50 °C (-4…+122 °F)
Storage and Transportation Temperature Range
-25...+85 °C (-13…+185 °F)
Altitude 2000
m
Humidity 5…95%
(non-condensing)
Pollution Degree
3
Enclosure Ratings
IP66/UL Type 4/12 ➊
Approximate Shipping Weight
4.6 kg (10 lb)
Mechanical Ratings
Resistance to Shock
Operational
30 G, exceeds IEC 60947-1
Non-Operational
50 G, exceeds IEC 60947-1
Resistance to Vibration
Operational
2.5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Non-Operational
5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Disconnect Lock Out
Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks
Up to 2 locks or hasps are supported
Disconnect Mechanical Life
200 000 operations
Contractor Utilization Category
(IEC)
AC-1, AC-3, AC-4 (refer to Life Load Curves)
Contactor Opening Delay
8…12 ms
Contactor Closing Delay
18…40 ms
Minimum Off Time
200 ms
Contactor Mechanical Life
15 million operations
Power Terminals
Motor Terminals
Control Terminals
PE/Ground
Wire Size
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per terminal
#18…#10 AWG
(0.8…5.2 mm
2
) per terminal
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per terminal
(2) #16 …#10 AWG
(1.3…5.2 mm
2
) per terminal
Wire Type
Multi-strand copper wire
Tightening Torque
10.6 ± 2 lb•in (1.2 ± 0.2 N•m)
18 ± 2 lb•in (2 ± 0.2 N•m)
Wire Strip Length
0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating
600V AC/25 Amp VAC
600 V AC/10 Amp VAC
600 V AC/10 Amp VAC
—
Emission and Immunity Ratings
Emission
Conducted
EN 60947-4-1
Class A
Radiated
Electrostatic Discharge
4 kV contact, 8 kV air
Radio Frequency Electromagnetic Field
EN 60947-4-1
10V/m, 80 MHz…1 GHz
10V/m, 1.4 GHz…2 GHz
Immunity
Fast Transient
2 kV (Power)
2 kV (PE)
1 kV (Communication and control)
Surge Transient
1 kV (12)
L-L
, 2 kV (2)
L-N
(earth)
Radio Frequency Conducted Disturbance
10V, 150 kHz…80 MHz
➊ IP66/UL Type 4 is available with gland options G1-3. IP66/UL Type 4/12 available with G1 and G3 gland option