Specifications
Chapter 6
Environmental Ratings
Operating Temperature Range
-20…+40 °C (-4…+104 °F)
50 °C (122 °F) without derating, when properly rated line reactors are installed
in branch circuit.
Storage and Transportation
Temperature Range
–25...+85 °C (–13…+185 °F)
Altitude
1000 m
Humidity
5…95% (non-condensing)
Pollution Degree
3
Enclosure Ratings
IP66/UL Type 4/12 ➊
Approximate Shipping Weight
7.3 kg (16 lb)
➊ IP66/UL Type 4 is available with gland options G1-3. IP66/ UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Resistance to Shock
Operational
30 G (exceeds IEC 61800-5-1)
Non-Operational
50 G (exceeds IEC 61800-5-1)
Resistance to Vibration
Operational
2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Non-Operational
5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Disconnect Lock Out
Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks
Up to 2 locks or hasps are supported
Disconnect Mechanical Life
200 000 operations
Power Terminals
Motor Terminals
Control Terminals
PE/Ground
Source Brake
Wire Size
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
#18…#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #16 …#10 AWG
(1.3…5.2 mm
2
) per
terminal
#16 …#10 AWG
(1.0…4.0 mm
2
) per
terminal
Wire Type
Multi-strand copper wire
Tightening Torque
10.6 ± 2 lb•in (1.2 ± 0.2 N•m)
18 ± 2 lb•in
(2 ± 0.2 N•m)
4.8 ± 2 lb•in
(0.5 ± 0.2 N•m)
Wire Strip Length
0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating
600V AC/25 Amp VAC
600V AC/10 Amp VAC
600V AC/10 Amp VAC
—
600V AC/10 Amp VAC
Emission and Immunity Ratings
Emission
Conducted
EN 55011
Class Group 2
Radiated
Electrostatic Discharge
4 kV contact, 8 kV air
Radio Frequency Electromagnetic Field
EN 61800-3
10V/m, 80 MHz…1 GHz
Immunity
Fast Transient
2 kV (Power)
2 kV (PE)
1 kV (Communication and control)
Surge Transient
1 kV (12)
L-L
, 2 kV (2)
L-N
(earth)
Radio Frequency Conducted Disturbance