Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 187
![background image](/manuals/578111/187/background.png)
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
187
Specifications
Chapter 6
EtherNet/IP
EtherNet/IP ODVA - Conformance Testing
EtherNet/IP Interoperability Performance – Per A9 PF 2.1
Ethernet Communication Rate
10/100 Mbps, half or full-duplex
Ethernet Ports
2 (embedded switch)
Ethernet Network Topologies Supported
Star, Tree, Linear, and Ring
Device Level Ring Support
Beacon Performance, IEEE 1583 Transparent Clock
Ethernet Connector
M12, D code, female, with Ethernet keying, 4 Pin
Ethernet Cable
Category 5e: Shielded or unshielded
IP Configuration
Static, DHCP, or BootP
DHCP Timeout
30 s
Data
Transported over both TCP and UDP
Packet Rate (pps)
500 packets-per-second (2000 μs), Tx
500 packets-per-second (2000 μs), Rx
Consume Instance (Command)
Default of 4 words (Instance 154)
Produce Instance (Status)
Default of 16 words (Instance 156)
Message Support
Unicast or Multicast
Address Conflict Detection (ACD)
IP v4 Address Conflict Detection for EtherNet/IP devices
Sockets
150 maximum
Web Server
Security
Login and password configurable
Support Simple Mail Transfer Protocol (SMTP)
Webpage Features
Status, diagnostics, configuration
Concurrent Sessions
20
Web Server
HTTP 1.1
Network Connections
Concurrent TCP Connections
Maximum of 5 encapsulated messages over both TCP and UDP
Maximum I/O Connections (CIP Class 1)
Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or
listen-only]. One connection per PLC. Listen-only connection
requires a data connection to be established.
Maximum Concurrent Explicit Messages (CIP Class 3)
6
Class 1 Connection API
2…3200 ms
Class 3 Connection API
100…10 000 ms
Request Packet Interval (RPI)
20 ms default (2 ms minimum)
Communication Ratings