The following common services will be implemented for the Identity Object:
Message Router
CLASS CODE 0x0002
No class or instance attributes will be supported. The message router object exists
only to route explicit messages to other objects.
DeviceNet Object
CLASS CODE 0x0003
The following class attributes will be supported for the DeviceNet Object:
A single instance (instance 1) of the DeviceNet Object will be supported. The
following instance attributes will be supported.
➊ Allocation_byte
Bit 0 Explicit messaging
Bit 1 Polled I/O
Bit 4 COS I/O
Bit 5 Cyclic I/O
Bit 6 Acknowledge Suppression
4
Non-volatile configuration bad
5
Major fault – either bit 10 or bit 11 is true (1)
6
At least one I/O connection in run mode
7
At least one I/O connection established, all in idle mode
Service Code
Implemented for:
Service Name
Class
Instance
0x01 No
Yes
Get_Attributes_All
0x05 No
Yes
Reset
0x0E Yes
Yes Get_Attributes_Single
0x010 No
Yes
Set_Attributes_Single
Value
Description
Attribute ID
Access Rule
Name
Data Type
Value
1
Get Revision
UINT
2
Attribute ID
Access Rule
Name
Data Type
Value
1
Get/Set
Node Address
USINT
0 - 63
2 Get/Set
Baud Rate
USINT
0 = 125K
1 = 250K
2 = 500K
5 Get
Allocation Info
Allocation Choice
Master Node Addr
Structure of:
BYTE
USINT
Allocation_byte➊
0 - 63 = address
255 = unallocated
6
Get
MAC ID Switch Change
BOOL
8
Get
MAC ID Switch Value
USINT
0 - 63