Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 237

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
237
CIP Information
Appendix B
A single instance of the DPI Alarm Object will be supported.
The following common services will be implemented for the DeviceNet Interface
Object.
Attribute
ID
Access
Rule
Name
Data Type
Min/Max
Default
Description
15
Get/Set
Autobaud Enable
BOOL
0 -1
1
1= enabled; 0 = disabled
16
Get/Set
Consumed Assy
USINT
0 to 85
150 (drive 154)
See assembly instance definitions
for legal values
17
Get/Set
Produced Assy
USINT
100 to 190
151 (drive 155)
See assembly instance definitions
for legal values
19
Get/Set
Set to Defaults
BOOL
0 to 1
0
0=No action; 1=Reset
100
Get
Build
USINT
Firmware Build Number
101
Get
PTableinit errs
USINT
103
Get
Fan Data
Fan RPM
Fan Tach Pulses
Fan Control
Struct of
UINT
UINT
WORD
104
Get
Hardware Fault Data
Struct of
WORD
UINT
UINT
UINT
Bit0 = Forward Status
Bit1 = Reverse Status
Bit 2 = Disconnect On
Bit 3 = Brake Contactor
Bits 5-13 = unused
Bit 14 = CT Present error
Bit 15 = Power 24
Status Board Error
Present
Status Board Total Error
Present Conditions
Status Board Total Read
Errors
105
Get
Boot Rev
STRUCT of
USINT
USINT
Major rev
Minor rev
106
Get
NVS Object Init Errors
Struct of
UINT
Array of UINT
Number of Errors
List of CIP Objects that failed
107
Get
Error Data Structure
Struct of
DWORD
DWORD
DWORD
Service Code
Implemented for:
Service Name
Class Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single