Chapter 4, Bulletin 290d/291d/294d programmable parameters, Electronic data sheet (eds) – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 85: Basic setup parameters, Chapter

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
85
Chapter
4
Bulletin 290D/291D/294D
Programmable Parameters
Electronic Data Sheet (EDS)
An embedded EDS file can be uploaded directly from the ArmorStart LT. EDS
files are also available on the internet at:
http://www.ab.com/networks/eds
.
Basic Setup Parameters
Table 19 lists the minimum setup configurations required for Bulletin 290D/
291D or Bulletin 294D.
RSLogix 5000 is the recommended commissioning software. Download the Add-
On-Profile (AOP) from
for additional functionality. There are additional capabilities that are
not enabled or left at their default values.
Table 19 - Quick Parameter Setup
Bulletin 290D/291D
Bulletin 294D
28 FLASetting
29 OLResetLevel
30 OverloadClass
49 IOPointConfiguration
28 MotorNPVolts
29 MotorNPHertz
30 MotorOLCurrent
32 StopMode
34 MinimumFreq
35 MaximumFreq
36 AccelTime1
37 DecelTime1
49 IOPointConfiguration
IMPORTANT
All I/O points are configured as inputs, by default. Identify which points
are outputs, when needed for proper operation, using parameter 49
[IOPointConfiguration].