Appendix B
CIP Information
The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.
Service Code
Implemented for:
Service Name
Class Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
No
Set_Attribute_Single
Table 30 - Fault Codes, Fault Text, and Fault Help Strings for DOL and Reversers
Fault
Code
Fault Text
Help Text
1
Fault 1
—
2
User Defined
User defined trip has occurred.
3
Overload Trip
Load has drawn excessive current based on trip class selected.
4
Fault 4
—
5
Phase Loss Trip
Indicates missing supply phase. This fault can be disabled.
6
Jam Trip
Motor current above jam level for more than jam trip delay time.
7
Underload Trip
Motor current below UL level for more than UL trip delay time.
8
Fault 8
—
9
Fault 9
—
10
Fault 10
—
11
Fault 11
—
12
Stall Trip
Motor current above stall trip level during motor starting.
13
Switched Power
Indicates the loss of switched control power.
Not available in units with Integrated Power Supply.
14
Under Power Trip
Indicates the internal power supply is below its working level.
Available in units with Integrated Power Supply only
15
Sensor Short
Flags a miswired hardware input point.
16
Output Short
Flags a miswired hardware output point.
17
Fault 17
—
18
Fault 18
—
19
Phase Imbalance
Indicates an imbalanced phase current.
20
Fault 20
—
21
Aux Power Loss
Auxiliary Power was lost or dipped below the minimum threshold.
Not available in units with Integrated Power Supply
22
Fault 22
—
23
Fault 23
—
24
Fault 24
—
25
Fault 25
—
26
Fault 26
—
27
NonVol Memory
This is a major fault which renders the unit inoperable.
28
Fault 28
—
29
Fault 29
—