Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 150

150
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
AutoRstrtDelay
Sets time between restart attempts when
Parameter 84(Auto Rstrt Tries) is set to a
value other than zero.
Parameter Number
85
Related Parameter
84
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
0.0
Maximum Value
120.0
Default Value
1.0
BoostSelect
Sets the boost voltage (% of Parameter 28
[MotorNPVolts]) and redefines the Volts
per Hz curve.
See Table 21 for details.
Parameter Number
86
Related Parameters
28, 29
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
—
Minimum Value
1
Maximum Value
14
Default Value
8
Table 21 - Boost Select Options
Options
Description
Custom V/Hz
Variable Torque
(Typical fan/pump curves)
1
30.0, VT
2
35.0, VT
3
40.0, VT
4
45.0, VT
5
0.0 no IR
Constant Torque
6
0.0
7
2.5, CT
8
5.0, CT (default)
9
7.5, CT
10
10.0, CT
11
12.5, CT
12
15.0, CT
13
17.5, CT
14
20.0, CT