Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 132

132
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
MotorNPHertz
Set to the motor nameplate rated
frequency.
Parameter Number
29
Access Rule
GET/SET
Data Type
UINT
Group
Motor and Control
Units
Hz
Minimum Value
10
Maximum Value
400
Default Value
60
Stop drive before changing this
parameter.
O
MotorOLCurrent
Set to the maximum allowable motor current.
Parameter Number
30
Related Parameter
31, 80, 82…83
Access Rule
GET/SET
Data Type
UINT
Group
Motor and Control
Cat. No.
Hp (kW)
Min Amps
Default Amps
Units
x.x Amps
294_FD1P5
0.5 (0.4)
0
1.5
Minimum Value
0
294_FD2P5
1.0 (0.75)
0
2.5
Maximum Value
Cat. No. Dependent
294_FD4P2
2.0 (1.5)
0
3.6
Default Value
Cat. No. Max Output
CurrentLimit
Maximum output current allowed before current limiting occurs
Parameter Number
31
Related Parameters
Access Rule
GET/SET
Data Type
UINT
Group
Motor and Control
Cat. No.
Hp (kW)
Units
x.x Amps
294_FD1P5
0.5 Hp
Min = 0; Max = 2.7; Default = 2.2
Minimum Value
0
294_FD2P5
1.0 Hp
Min = 0; Max = 4.5; Default = 3.7
Maximum Value
Cat. No. Dependent
294_FD4P2
2.0 Hp
Min = 0; Max = 7.5; Default = 6.3
Default Value
Cat. No. Dependent
StopMode
Valid Stop Mode for the Bulletin 294E ArmorStart LT are the following:
0 = RampToStop, “Stop” command clears active fault
1 = Coast to Stop, “Stop” command clears active fault
2 = DCBrake, DC Injection Braking Stop, “Stop” command clears active fault
3 = DCBrakeAuto, DC Injection Stop with Auto Shutoff
Standard DC Injection Braking for value set in Parameter 75 (DC Brake Time)
or
Drive shuts off if current limit is exceeded.
Parameter Number
32
Related Parameters
Access Rule
GET/SET
Data Type
UINT
Group
Motor and Control
Units
—
Minimum Value
0
Maximum Value
3
Default Value
0