Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
Input01Function
This parameter determines the special
function for User Input 1:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive. All
others are edge sensitive
Parameter Number
59
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
4
Default Value
0
Input02Function
This parameter determines the special
function for User Input 2:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive. All
others are edge sensitive
Parameter Number
60
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
4
Default Value
0
Input03Function
This parameter determines the special
function for User Input 3:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive. All
others are edge sensitive
Parameter Number
61
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
4
Default Value
0
Input04Function
This parameter determines the special
function for User Input 4:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊
➊ These choices are level sensitive. All
others are edge sensitive
Parameter Number
62
Access Rule
GET/SET
Data Type
USINT
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
4
Default Value
0