Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
StallTripLevel
This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.
Parameter Number
75
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
100
Maximum Value
600
Default Value
600
ULInhibitTime
This parameter determines the time
during motor starting that Underload
detection is inhibited.
Parameter Number
76
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs
Minimum Value
0
Maximum Value
250
Default Value
10
ULTripDelay
This parameter determines the time below
Underload Level before the unit will trip.
Parameter Number
77
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
1
Maximum Value
25.0
Default Value
5.0
ULTripLevel
This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.
Parameter Number
78
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
%FLA
Minimum Value
10
Maximum Value
100
Default Value
50