Speed control group – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual
Page 133

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012
133
Bulletin 290D/291D/294D Programmable Parameters
Chapter 4
Speed Control Group
SpeedReference
Sets the source of the speed reference:
0 = Logix (Network or DeviceLogix)
1 = InternalFreq
Parameter Number
33
Related Parameters
1, 2, 36, 37, 72
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
—
Minimum Value
0
Maximum Value
2
Default Value
0
MinimumFreq
Sets the lowest frequency the drive will
output continuously.
Parameter Number
34
Related Parameter
1, 2, 35
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
x.x Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
0.0
MaximumFreq
Sets the highest frequency the drive
will output.
Parameter Number
35
Related Parameter
1, 2, 34, 35, 139
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
Hz
Minimum Value
0.0
Maximum Value
400
Default Value
60
Stop drive before changing this
parameter.
O
AccelTime1
Sets the rate of acceleration for all speed increases.
Parameter Number
36
Related Parameters
33, 37
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
x.x secs
Minimum Value
0.0
Maximum Value
600.0
Default Value
10.0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 1
0
0
Time
Decel
Time 1
Ac
celer
ation
Dec
eler
ation