Chapter 4
JamTripDelay
This parameter determines how much
time above the Jam Level before the unit
will trip.
Parameter Number
71
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
1
Maximum Value
25.0
Default Value
5.0
JamTripLevel
This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.
Parameter Number
72
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
50
Maximum Value
600
Default Value
250
JamWarningLevel
This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.
Parameter Number
73
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
50
Maximum Value
600
Default Value
150
StallEnabledTime
This parameter determines the time
that stall detection is enabled during
motor starting.
Parameter Number
74
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs
Minimum Value
0
Maximum Value
250
Default Value
10