beautypg.com

Did trunks troubles – AT&T System 25 User Manual

Page 269

background image

MAINTENANCE

8.

9.

10.

11.

12.

If the problem does not move, replace the Ground Start CP.

If the problem moves, the fault is with the CO. Notify CO personnel

through the proper channels.

If “Ringing no ground” is displayed, the T and R leads may be

reversed in the trunk access wiring. The T lead should have ground,
and the R lead should have –48 volts. These can be verified by
reversing the ground and ring leads and checking with either a

voltmeter or a test set (with a polarity switch). A voltmeter should
indicate the presence
when the Ring lead is

“Ringing no ground”

on the Ground Start
necessary.

"Ringing no ground”

of 48 volts. A test set should provide dial tone

temporarily grounded.

may also mean that the ground detect circuit

CP is faulty. Check and replace this CP if

may also mean that the CO is unable to send

ground. If this is the problem, notify the CO through the proper
channels.

DID Trunks Troubles

Symptoms:

User complaints that DID trunks are not operating properly (for

example, callers hear ringing, but users do not hear ringing at voice
terminals).

P r o c e d u r e s :

1.

Check the trunk translations via the SAT to be sure that trunks have
been properly translated. (See the

Administration Manual.)

2. Check the Error Log for messages such as:

Rotary dial

Rotary dial

Rotary dial

before wink

pulse too early

pulse during wink

4-92