4. Commissioning
4−28
Festo P.BE−SPC200−COM−PDP−E N en 0901c
Bit
Explanation
Meaning
5
Sync_Req
log. 1": Activate SYNC
6
7
Unlock_Req
Lock_Req
Bit 7
Bit 6
0
0
0
1
1
0
1
1
min T
SDR
+ SPC200 parameters may be
overwritten
SPC200 released for other masters
SPC200 blocked for other masters
SPC200 released for other masters
Bytes 2 and 3:
WD_Fact_1
WD_Fact_2
Bit
Meaning
Explanation
Range 1...255:
The response monitoring time of the SPC200 is transmitted with these two
bytes: T
WD
[s] = 10ms * WD_Fact_1 * WD_Fact_2
Byte 4: Minimum station delay responder (min T
SDR
)
Bit
Meaning
Explanation
The minimum time the SPC200 must wait, before the reply telegram may
be sent to the DP master.
Bytes 5 and 6: Ident_number
Bit
Meaning
Explanation
Transmission of the Ident number (= 00C8
H
) of the SPC200.
Parametrizing telegrams to the SPC200 are only accepted if the