4. Commissioning

4−21

Festo P.BE−SPC200−COM−PDP−E N en 0901c

4.4.6 DP identifier for transmission of the setpoint positions (optional)

In order to transmit the setpoint positions you will require:

ć

fieldbus module with firmware version as from V 2.1

ć

SPC200 with operating system version as from V 4.82

ć

WinPISA as from version 4.41.

During transmitting of the setpoint positions, data conĆ
sistency is only permitted over the complete length. The DP
identifier must be entered separately for each axis.

Setpoint

iti

Address space

DP identifiers

position

EN 50170

Siemens

EN 50170

Siemens

Consistent over

1 byte

complete length

2 output words

2 output words

*)

*)

E1

h

225

d

*) Data consistency only permitted over complete length!

Fig. 4/11: DP identifier for transmitting the setpoint positions

The assignment on the relevant axes is made in the confiĆ
gured sequence. DP identifiers for non−configured axes are
not permitted.

ć

First DP identifier for setpoint position (DP identifier with
the lowest slot number): X−axis

ć

Second DP identifier for setpoint position: Y−axis

ć

Third DP identifier for setpoint position: Z−axis

ć

Fourth DP identifier for setpoint position: U−axis

Setpoint positions

Value range

ć99.999.900 ... +99.999.900

Unit

0,1 Ģm

Setpoint positions: ć9.999,99 ... +9,999.99 mm (Integer32, s. A.1.5)